2 . SLOW-BLOW TYPE

 

 

 

 

51S/52S
GLASS TUBE FUSE (Slow-blow) 

 

   

  TEST SPECIFICATION

% of Ampere Rating

Openning Time

110%

4 hours, Minimum

135%

1 hour, Maximum

200%

5 sec~2 Minutes

  UL File No.E236987
    51S/52S  125V  300mA-3.5A(Listed)
                          4A-8A(Recongnized) 
    51S/52S  250V  300mA-3.5A(Listed)
                          4A-8A(Recongnized)  

  CSA Certified file No.1433145/1438084
    51S/52S  125V  300mA-3.5A(Listed)
                          4A-8A(Recongnized) 
    51S/52S  250V  300mA-3.5A(Listed)
                          4A-8A(Recongnized)  

  Interrupting Rating

10,000 amperes at  125V
AC (300mA-3.5A)

500 amperes at 125V
AC (4A-8A)

35 amperes at       250V
AC (300mA-1A)

100 amperes at 250V
AC (1.2A-8A)

RATINGS

51S, 52S Cat. No

Ampere

    0500 H/L

    0600 H/L

    0630 H/L

    0750 H/L

    0800 H/L

    010 H/L

    013 H/L

    015 H/L

    016 H/L

    020 H/L

    025 H/L

    030 H/L

    032 H/L

    035 H/L

    040 H/L

    050 H/L

    060 H/L

    063 H/L

    070 H/L

    080 H/L

    500mA

    600mA

    630mA

    750mA

    800mA

    1A

    1.25A

    1.5A

    1.6A

    2A

    2.5A

    3A

    3.15A

    3.5A

    4A

    5A

    6A

    6.3A

    7A

    8A

H denotes for 250V / L denotes for 125V
 

    

  

 
TIME-CURRENT CHARACTERISTICS

 

 

 Copy right 2004 by DAINFUSE Co., Ltd. All Right Reserved   Mail to dainmaster